Large Power System 36 - 288kW
The Large Power System proves that Flatpack2 and DPR 6000 is the ultimate building block in any telecom application. The combination of a flexible design, power density and reliability makes the Flatpack2 and DPR 6000 a product family that truly stands outs and provides unparalleled network availability.
The versatility of the Flatpack2 and DPR 6000 rectifier means that it can be used in a wide variety of DC applications across the globe.
The versatility of the Flatpack2 and DPR 6000 rectifier means that it can be used in a wide variety of DC applications across the globe.
Overview
Large Power System 36 - 288kW
Eltek's Large Power System can be equipped with either Flatpack2 2kW, Flatpack2 3kW or DPR 6000 rectifiers. Basic configuration with Flatpack2 2kW rectifiers is with six power shelves with the possibility to expand up to 12 (in steps of three).
Basic configuration with Flatpack2 3kW rectifiers is with three power shelves with the possibility to expand up to 9 (in steps of three). Basic configuration with DPR 6000 rectifiers is with two power shelves with possibility to expand up to 4 (in steps of one).
Basic configuration with Flatpack2 3kW rectifiers is with three power shelves with the possibility to expand up to 9 (in steps of three). Basic configuration with DPR 6000 rectifiers is with two power shelves with possibility to expand up to 4 (in steps of one).
Key features
- System monitoring
- Flatpack2 modules
- DPR6000 modules
- Full height lockable door
- Dummy panels and unit doors
- Configurable mains input
- Surge protection device
- LVBD (Low Voltage Battery Disconnection)
- LVLD (Low Voltage Load Disconnection)
- Cabinet paraleling for expanded power or additional distributions
Technical Data
Input
Max input AC Voltage
305 VAC
Mains configuration
230VAC Single phase;230VAC 3 phase (Δ);230/400VAC 3 phase (Y)
DC Output
Current (maximum)
2250 ADC
Max voltage
48 VDC
Max power
108 kW
Battery Distribution
Breaker positions up to
4
Breaker rating up to
1600 A
LVBD
Yes
DC Load Distribution
Breaker positions up to
8
Breaker rating up to
600 A
LVLD
Yes
Other
Options
MCB distributions, Intern cabinet connection links, Low Voltage Battery disconnect, Low Voltage Load disconnect, Top or Bottom cable entry
Mounting Type
Floor
Dimensions
Dimensions WxHxD (mm)
600 x 600 x 2000 mm
Dimensions WxHxD (inch)
15,2 x 15,2 x 78,7 "
Design Standards
Ingress Protection (IP)
20
Downloads ()
-
Datasheet Large Power Systems FPC
- Version 5
- 1209 kB
- Document number: 271431.DS3
Request a quote