Scalable DC power system

The Eltek acalable DC power system offers an array of configurable components that come together to produce large-scale, high-power solutions—up to half a million watts!
Overview

Scalable DC power system

Eltek’s scalable line of power solutions is comprised of configurable components designed to meet the needs of Central Offices and other high-power DC applications.A variety of rectifier bays provides 48V DC output ranging from 3000A to 20,000A (if cabled).

Distribution options offer everything from bulk output to circuit breakers, fuses, and even overhead bus arrangements with shunts.

Key features

  • Plant Configurations
  • Scalable plant design consists of at least one main rectifier bay with master controller
  • Additional rectifier and distribution bays can be directly linked together by bus bars
  • Bays can be configured side-by-side in any orderTwo bay models for three-phase Powerpack rectifiers
  • Accommodates up to 15 rectifiers
  • Output DC current of up to 3000A per bay
  • DC bus available in 3000A, 6000A, and 10,000A ratings
  • Control and monitoring devicesBulk bus on each bay
  • 3000A, 6000A, and 10,000A ratings available
  • Bottom-feed buses available
  • Distribution bays
  • 48 configurable distribution positions
  • Modules available for small and large circuit breakers and fuses
  • Alarm and shunt monitoring
  • Internal bus work rated for 3000A or 6000A
  • High-current bay shunt (either 4000A or 8000A)
  • Top and bottom cable access
  • Interactive controller display on primary rectifier bay (Smartpack2 Master)
  • 12 alarm inputs and outputs available
  • Distribution alarm and shunt monitors in distribution bays
  • Optional add-on devices for monitoring alarms, shunts, temperatures, and voltages at several points.
Technical Data
Input
Current (maximum)
10000 ADC
Voltage AC (operating range)
208 - 480 VAC
Voltage DC (operating range)
43 - 56 VDC
Max input AC Voltage
530 VAC
Max input DC Voltage
56 VDC
Electrical
Power consumption
4.5 W
MTBF
1300000 h
System connections
Voltage
1 or 3
Current
1 or 2
Battery
(1) Midpoint
Load
Ground fault detection
Output
Output
Form-C Dry Contact (NO-C-NC) Max 75V
Configurable inputs
Number of configurable inputs
12
Digital configurations
#1-12: Open/Closed
Number of analog configurations
3
Analog configurations
Temperature: NTC probe Analog:+/-0-10V 4-20mA current sensing
DC Output
Max Power
11000 W
Voltage (adjustable range)
43 - 56 VDC
Current (maximum)
10000 ADC
Max voltage
56 VDC
Max power
165 kW
LVD
Batteries
0
Loads
0
Ports
Available ports
Ethernet;RS-282;RS-485
Display
Size
3,2 "
Resolution
QVGA 32k color TFT
Battery Distribution
Breaker positions up to
0
DC Load Distribution
Breaker positions up to
48
Breaker rating up to
1200 A
LVLD
No
GJ Breaker/TPL Fuse Panel
<div class="ExternalClass2FBA4FA4A0DA49188DA2F6B43839DE81"><html> <p>​48 Pole Positions </p> </html></div>
Bulk Connections
<div class="ExternalClassF789C7BFB8274DECA6C55D8523DDFC15"><html> <p>​8</p> </html></div>
AC Load Distribution
Number of breakers
8
Breaker rating, up to
60 A
Other
Cooling
Double fan
Efficiency
94 %
Operating temperature
-10 - 40 °C
Storing temperature
-40 - 70 °C
Mounting Type
Floor
Dimensions
Dimensions WxHxD (inch)
23,6 x 84 x 25,3 "
Weight
753 lbs
Certifications
UL
UL 60950-1
Telcordia approvals
NEBS GR1089-CORE;NEBS GR63 CORE Zone 4
Software functionality
Rectifier Functions/Monitoring
o Individual Rectifier Current Measurement o Individual Rectifier Input Voltage o Efficiency Management o Emergency Voltage o Startup delay o Detailed internal alarms summary
Downloads ()
Request a quote
Not right? Choose correct location
Your message will be sent to your closest Eltek Office
To the top