Rectiverter Power Core 18kVA 1ph or 3ph MB
The Rectiverter power core combines both AC and DC feed into one common unit. Simultaneously it provides AC backup power for 3-phase or single phase AC loads, and 48 Vdc power for DC loads and battery charging.
Overview
Rectiverter Power Core 18kVA 1ph or 3ph MB
The total output power for booth AC and DC output is limited to max 24kW. AC and DC output limits can be set according to the attached load, where the limitation for AC load is set to max 18kVA and for DC load to max 14,4kW
Key features
- 230/400 Vac input/output
- Three phase (y) input/output One phase input/output
- 48 Vdc input/output
- 24kW total AC + DC output
- Max 18 kVA AC output
- Max 14,4kW DC output
- 1phase AC distribution option
- 3phase AC distribution option
- Built in manual bypass switch
- Built in transfer technology
- 150% overload capability, 15s
- 600% quick trip current, 20ms
- Hot pluggable
- Smartpack2 controller
Technical Data
Input
Current (maximum)
384 ADC
Voltage AC (operating range)
174 - 220 VAC
Max input AC Voltage
475 VAC
Max input DC Voltage
58 VDC
Mains configuration
230/400VAC 3 phase (Y);230VAC Single phase
AC Output
Max Output AC Voltage
415 VAC
DC Output
Max Power
14400 W
Voltage (adjustable range)
43 - 58 VDC
Current (maximum)
300 ADC
Max voltage
58 VDC
Max power
14,4 kW
AC Load Distribution
Number of breakers
18
Breaker rating, up to
20 A
Other
Operating temperature
-40 - 55 °C
Dimensions
Dimensions WxHxD (mm)
482 x 311 x 432 mm
Dimensions WxHxD (inch)
18,98 x 12,24 x 17,01 "
Mounting dimensions
19" / 7U / 432 Width (Inch) / Height (U) / Depth (mm)
Weight
27 kg
Design Standards
Ingress Protection (IP)
20
Downloads ()
-
Rectiverter Power Core 18 kVA 1ph or 3ph MB
- Version 3
- 834 kB
- Document number: CIOR1207.DS3
Request a quote