Ultron DPS 160-500kVA
                    The excellent power performance and high system availability of the Ultron DPS range provides customers with the benefits of a stable power supply, high power efficiency, low capital investment and low overall operational cost.
                
                
            
    Overview
    
        
            
        
            
                    
        
    
Leading in power performance and efficiency
                The Ultron DPS series UPS is a double-conversion and IGBT-rectifier three phase UPS. With the three level IGBT topology for both power factor correction (PFC) and inverter, the Ultron DPS features industry leading performance of upto 96% AC/AC efficiency. Thanks to the advanced digital PFC control, it also has low iTHD <3% and high input power factor >0.99 resulting in significant total cost of ownership (TCO) savings. 
Aiming to achieve the highest availability possible, the Ultron DPS has enhanced designs for battery management, swappable, fans and ease of maintenance.
            
        Aiming to achieve the highest availability possible, the Ultron DPS has enhanced designs for battery management, swappable, fans and ease of maintenance.
Key features
- N+X redundancy or hot-standby configuration increases system reliability
- Wide input voltage range allows the UPS to work in harsh electrical environments
- Field programmable sequential start-up
- Intelligent fan speed control and redundant fan design prevent overheating
- Comprehensive battery management sustains battery lifetime and optimal operation
- High efficiency even at light load saves operating costs
- High input power factor greater than 0.99, and low input harmonic distortion (less than 3%) save upstream investment
- Parallel expansion without extra hardware allows quick capacity upgrade tomeet business growth
- Swappable fans reduce maintenance lead time
- Built-in manual bypass allows “zero downtime” to ensure system availability during service maintenance
- Main I/P and O/P switches detection provide quick diagnosis when faults occur
    Technical Data
    
            
        
    
                Input
                
                        
                            
                        
                            
                        
                            
                
            
            Voltage AC (operating range)
                            242 - 477 VAC
                        Max input AC Voltage 
                            415 VAC
                        Mains configuration
                            230/400VAC 3 phase (Y)
                        
                AC Output
                
                        
                            
                        
                            
                
            
            Max Output AC Voltage
                            415 VAC
                        Max power (kVA/kW)
                            500 / 450
                        
                Configurable inputs
                
                        
                            
                
            
            Number of configurable inputs
                            7
                        
                Ports
                
                        
                            
                
            
            Available ports
                            RS-282;USB;RS-485;Ethernet
                        
                Battery Distribution
                
                        
                            
                        
                            
                        
                            
                
            
            Breaker positions up to
                            1
                        Breaker rating up to
                            600 A
                        LVBD
                            Yes
                        
                AC Load Distribution
                
                        
                            
                        
                            
                
            
            Number of breakers
                            1
                        Breaker rating, up to
                            800 A
                        
                Other
                
                        
                            
                        
                            
                
            
            Operating temperature
                            0 - 45 °C
                        Mounting Type
                            Floor
                        
                Dimensions
                
                        
                            
                        
                            
                        
                            
                
            
            Dimensions WxHxD (mm)
                            1600 x 1950 x 865 mm
                        Dimensions WxHxD (inch)
                            63 x 76,8 x 34,1 "
                        Weight
                            1220 kg
                        
                Design Standards
                
                        
                            
                
            
    Ingress Protection (IP)
                            20